GE IC300TIU201 Cell Phone User Manual


 
PAGE 26 06 Apr 2000 CH. 4: TIU110/111/112/113
GFK-1819
4.5.1 TIU11X Configuration of the RS-485 Port
The configuration bank (shown in Figure 4.8) sets the parameters of the RS-485 port as described in
Table 4.1.
Table 4.1 Configuration Bank
Switch 1 ON: Pull-up (must be used together with switch 3)
OFF: no Pull-up
Switch 2
ON: 120
termination
OFF: no termination
Switch 3 ON: Pull-down (must be used together with switch 1)
OFF: no Pull-down
Switch 4 Reserved for future use
NOTE:
Switch 1 and 3 must be used together. Either both pull-up and pull-down are
used or neither is used.
Pull-up
and
Pull-down
switches are used to increase the signal level on the RS-485 bus. This is useful if
there is a long bus and a significant amount of attenuation is anticipated.
Termination
resistance of 120
must be placed across each end of the RS-485 bus. With switch 2 ON,
a 120
resistance is placed across the bus. This should only be used if the TIU050/100/110 is the last
device at either end of the bus.
4.6 TIU11X Dimensions
TOLERANCES ARE +/- 0.01 [0.3mm] UNLESS STATED OTHERWISE
TIU11X CUTOUT DETAILS
3.27 [83 mm]
+0.02
-0.00
+0.5
-0.0
5.95 [151mm]
UP TO 0.04[1mm] CORNER
RADIUS IS ACCEPTABLE
Figure 4.8 TIU11X Cutout