13
EN
Battery
Autonomy time (for a battery charged 100% and at 25°C)
Autonomy time (nominal load, pf = 0.9 lag.)
Linked
battery modules
D.
1000 D. 1500 D. 2000 D. 3000
With integrated battery 6 min. 5.5 min. 6 min. 3.5 min.
1 extra battery module 31 min. 25 min. 33 min. 18 min.
2 extra battery modules 51 min. 46 min. 59 min. 34 min.
3 extra battery modules 82 min. 69 min. 88 min. 53 min.
4 extra battery modules 100 min. 90 min. 119 min. 69 min.
Rated direct voltage (intermediate circuit)
PROTECT D.
1000 36 V
PROTECT D.
1500 48 V
PROTECT D.
2000 72 V
PROTECT D.
3000 72 V
Float voltage 2.28 Vdc/cell (pre-set to 25°C)
charging voltage temperature dependent
Setting range 2.21 Vdc/cell – 2.31 Vdc/cell
in 0.01V increments
Batt.-charge power (max.) 1.4 Adc (PROTECT D.1000 / D.1500)
1.7 Adc (PROTECT D.2000 / D.3000)
Battery type Valve regulated lead battery (VRLA)
Special type for high-current discharge
PROTECT D.1000 3 blocks at 12V 9Ah
PROTECT D.1000 BP 2 belts at 3 blocks at 12V 9Ah
PROTECT D.1500 4 blocks at 12V 9Ah
PROTECT D.1500 BP 2 belts at 4 blocks at 12V 9Ah
PROTECT D.2000 6 blocks at 12V 9Ah
PROTECT D.3000 6 blocks at 12V 9Ah
PROTECT D.2030 BP 2 belts at 6 blocks at 12V 9Ah
Recharging times ~ 3h to 90% for internal battery
~9h
/ ~15h / ~21h / ~27h with 1 / 2 / 3 / 4 battery extension(s)