52 Rockwell Automation Publication 150-QS003D-EN-P - November 2013
Chapter 4 Operation and Troubleshooting
Table 25 - Port Assignment
Network and
Comm’s Loss
See Port
Number of
Fault (See
Table 25)
All DPI network loss
Communication disconnect at the
serial port
Check communication adapters and verify connection to the
SMC.
Reconnect each DPI connected device
Ground Fault 58 Running Ground fault current level has
exceeded programmed value
The delay time is too short for the
application
Check power system and motor; correct if necessary. Check
programmed ground fault levels to match application
requirements
Extend the delay time to match the application requirements
Line Power
Quality with
Phase Indication
52, 53, 54 Start or
Stop
Incoming 3-phase voltage
instability or distortion
High impedance connection
Check supply voltage for capability to start/stop motor;
check for loose connections on the line side or motor side of
the power wires
Verify and correct the input power quality
Internal 24V and
System Faults
36, 37 All Low line condition
Excessive load on internal 24V
supply
Check the control power and verify it is within the
specification; check the connections and grounding to the
SMC control terminals
Replace the control module
Display Fault HIM or
Software
Fault Code
Enabled Possible Causes Possible Solutions
Port Number Source
0 Control Module
1 HIM Located in Controller Bezel (optional)
2 or 3 Remote DPI
4 20-COMM-X (optional)
7, 8, 9 Expansion Port 7, 8, 9 (option module)