Turbomachinery Package Specification Taurus 70 Compressor Set and Mechanical Drive
Figure 23. Typical Water Mist Suppression Fire Cylinder Cabinet
Table 11. Enclosure Specifications
Enclosure
Optional Ventilation Fan Motor Voltage Ratings
380 VAC, 400 VAC, and 415 VAC (50 Hz)
460 VAC (60 Hz)
Primary Enclosure Lighting Voltage 220 VAC (50 Hz) or 110 VAC (60 Hz)
Standby Enclosure Lighting Voltage 120 VDC
Sound Pressure Level
See Note (a)
Enclosure Roof Load 244 kg/m
2
(50 lb/ft
2
)
Enclosure Wind Load 193 kph (120 mph)
Approximate Measurements
Height
2.9 m (9 ft. 6 in.), Does Not Include Ventilation
Ducting
Width 2.7 m (8 ft 10 in.
Driver Length 8 m (25 ft)
Driven Length (Single Body Compressor) 4.6 m (15 ft)
Approximate Weights
Gas Turbine Enclosure 5180 kg (11,420 lb)
Compressor Enclosure (Single Body) 5670 kg (12,500 lb)
Fire Suppression System Compliance
CO
2
Fire Suppression System
U.S. National Fire Protection Association (NFPA) 12
United States Coast Guard (USCG) CFR 46
Water Mist Fire Suppression System U.S. NFPA Code 750; USCG CFR 46
Water Mist Fire Suppression System
Minimum Operating Temperature 4°C (40°F), Optional Heater Available
© 2009 Solar Turbines Incorporated. All rights reserved. TPS70CSMD/309