INSTALLATION AND CLEARANCES

WARNING: Maintain the



INSTALLATION
Continued
Carefully follow the instructions below. This will
ensure safe installation into a masonry, UL127-
listed manufactured replace or listed vent-free
rebox enclosure.
Minimum Clearances For Side


A. Clearances from the side of the fireplace
cabinet to any combustible material and wall
should follow diagram in Figure 4.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and
protrudes 3
1
/
2
" from the wall. This combus-
tible material must be 4" from the side of the
replace cabinet (see Figure 4).
Note: When installing your gas logs into
a manufactured firebox, follow firebox
manufacturer’s instructions for minimum
clearances to combustible materials.
B.
Clearances from the top of the replace opening
to the ceiling should not be less than 42 inches.
Figure 4 - Minimum Clearance for
Combustible to Wall
*Minimum 16 inches from Side Wall
*
Example


  
    
18" 17" 14" 24" 20"
24" 17" 14" 28" 22"
30" 24" 17
1
/
2
" 42" 28
3
/
4
"

CLEARANCE TO

 18", 24", 30"
Side Wall 16"
 42"
Floor 5"
*Measured at 14" depth

Clearances

Note: If using a mantel, proceed to If Using
Mantel. If not using a mantel, follow the informa-
tion below.
You must have noncombustible material(s) above
fireplace opening. Noncombustible materials
(such as slate, marble, tile, etc.) must be at least
1/2 inch thick. With sheet metal, you must have
noncombustible material behind it. Noncombus-
tible material must extend at least 8" up (for all
models). If noncombustible material is less than
12", you must install the replace hood accessory
24" and 30" models only). See Figure 5, page 10,
for minimum clearances.

You must have noncombustible material(s) above
the replace opening. Noncombustible materials
(such as slate, marble, tile, etc.) must be at least
1/2 inch thick. With sheet metal, you must have
noncombustible material behind it. Noncombus-
tible material must extend at least 8 inches up (for
all models). If noncombustible material is less than
12", you must install the replace hood accessory.
Even if noncombustible material is more than 12",
you may need the hood accessory to deect heat
away from your mantel shelf. See Figures 5, 6 and
7, page 10, for minimum clearances.