Error Description Action
#6 Err. Unsupported
Point Address
Format<%s>
A message was received from an
unsupported device or the address of
the device is not in the correct
format/location.
Call Tech support.
decrement below zero
offset<%d> DA<%s>
The driver attempted to decrement the
trouble counting number to a number
less than 0.
This occurs due to poor synchronization
between the FieldServer and the Notifier
panel or because a problem existed before
connection.
3
. It will rectify
“System Normal” message. Check the
configuration file to identify the address
and memory area type mapped to this
offset and the Data Array which is causing
the error.
3
All Data Arrays on the FieldServer are initialized to zero on rebooting or starting up. A zero value in the Data Array assumes no problems with
the devices, but if a problem existed before the startup and the device comes out of problem, the FieldServer will attempt to decrease the
number of problems by 1 and this generates the error. Data from the FieldServer should not be considered reliable until the “System Normal”
message has been returned.