(PANEL VOLTAGE-APPLIANCE MIN. VOLT) X WIRE CONDUCTIVITY
TOTAL CURRENT DRAW
}
{
MAX. WIRE
DISTANCE =
(IN FEET)
WIRE CONDUCTIVITY
18AWG 60
16AWG 95
14AWG 153
12AWG 244
Includes wire to and from appliance. CAUTION: Applies only to regulated
supplies. Assumes all appliances are at the end of wire run (worst case).
HORN RATINGS
HORN
VOLTAGE
dBA @
10Ft. Per
UL464
dBA @
10Ft.
Anechoic
DC(mA)
FWR(mA)
16VDC
76-88 90 19 -
24VDC
76-88 92 26 -
33VDC
76-88 95 34 -
16VFWR
76-88 90 - 35
24VFWR
76-88 92 - 43
33VFWR
76-88 95 - 49
STROBE CURRENT RATING
DC (mA) FWR (mA)
Candela Voltage Inrush Peak Operating
Inrush Peak Operating
16 162 118 63 174 189 79
15 24 178 145 42 182 181 61
33 178 172 34 182 189 57
16 212 140 99 240 188 119
30 & 15/75 24 248 144 66 256 187 84
33 256 179 52 260 192 72
16 310 198 134 310 286 169
60 24 314 218 84 322 291 110
33 322 274 61 330 295 86
16 320 216 161 312 307 209
75 24 316 243 100 324 285 139
33 336 289 75 328 267 108
16 396 228 193 392 292 247
110 24 396 247 118 392 304 160
33 400 286 86 408 308 123
V. CHECKOUT AND TROUBLESHOOTING
1. Supply power to the system control panel. The auxiliary signaling appliances in the system should not be activated.
2. If the signal is activated:
· Check all smoke and fire detectors in the system to make sure they have not been activated.
· Check all wiring connections to make sure the signal detection circuits are not reversed or shorted together. Check wire color codes and traces.
· Verify that the jumpers are properly set on both the control module and signal appliance. If the jumper on the AVS44 is as shown in Fig. 3, the
horns will not produce any sound unless there is an input to the H+ and H- terminals on the control module.
3. To test the signal appliances, trip the auxiliary panel or activate the alarm circuit at the main control panel or activate one of the fire detection units in
the system. All auxiliary signals should be activated.
4. An operational test on this product should be conducted in accordance with National Standards or at a minimum annually and more often if dictated
by local and state codes or authorities having jurisdiction.
Pg. 3
Note: Units have been tested to O
O
C, 49
O
C and 93% humidity and are rated 20-30vdc/vFWR -20%, +10%, per
CAN/ULC S526-M87. The 15/75 model is rated 15cd per UL 1971 and CAN/ULC S526-M87. Units are rated
16-33vdc/vFWR absolute per UL464 and UL1971.