Troubleshooting 39
Off Off
Flashing
red
Off Off Off
On—1 beep
every 5
seconds
Yes
Battery test failure
("Battery condition" on
page 39)
Off
Flashing
red
Off Off Off Off
On—1 beep
every 5
seconds
No
Low battery—No utility
power ("UPS is on
battery" on page 42)
Off Off
Flashing
red
Off Off Off
On—1 beep
every 5
seconds
Yes
Batteries are
disconnected ("Battery
condition" on page 39)
Off Red Off Off Off Off
On—1 beep
every 5
seconds
Yes
On battery—No utility
power ("UPS is on
battery" on page 42)
Off
Flashing
red
Off Off
Flashing
red
Off
On—1 beep
every 5
seconds
Yes
On battery—Input
voltage is out of range
(on page 40)
Flashing
red
Flashing
red
Flashing
red
Flashing
red
Flashing
red
Flashing
red
On—
Continuous
No
Internal UPS fault
condition (on page 40)
Red Off Off Off Off Off
On—
Continuous
Yes
Battery condition (on
page 39)
Flashing
red
Off Off Off
Flashing
green
Off
On—
Continuous
Yes
REPO condition (on
page 41)
Off Off Off Red Off Off
On—1 beep
every 5
seconds
Yes
Site wiring condition
(on page 41)
Flashing
red
Off Off Off Off Red
On—
Continuous
Yes
UPS power capacity is
exceeded ("Overload
condition" on page 41)
For the location of individual LEDs, see "UPS front panel LED indicators (on page 8)."
Battery condition
Action:
1. Install the battery module. If the battery module is already installed, remove and reinsert the module.
2. Allow the UPS batteries to charge for 48 hours.
3. If the LED does not turn off, replace the batteries ("UPS battery replacement procedure" on page 35).
4. If the condition persists, contact an HP authorized service representative.
Bypass is out of range
The input voltage is not within ±12 percent of nominal voltage.
The UPS is receiving utility power that might be unstable or in brownout conditions. The UPS continues to
supply power to the connected equipment. If conditions worsen, the UPS might switch to battery power.
Action:
1. Check the input voltage and reconfigure the UPS ("Configuring the UPS" on page 27).
2. Contact a qualified electrician to verify that the utility power is suitable for the UPS.