T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0255—07 22
Fig. 48. Setup - Outputs - Options - Min Off/On Time.
1.3.3.2. MIN OFF or MIN ON
This is the minimum number of seconds of “off time” or
“on time” for all relays.
1. Press the X button to display the Min Off/On value.
2. Use the S and T buttons to increase/decrease the
desired number of seconds from 0 to 990 seconds
in 10 second increments.
Default: 0 (zero)
Range: 0 to 990 seconds
3. Press the X button to accept the seconds and
display the DI OPTIONS.
NOTES:
1. The minimum off time applies to all relay
outputs.
2. When minimum off time is active, relays
waiting to be energized display a flashing
square underneath the relay number on the
home screen.
3. If the minimum off time is not equal to zero
(0), the minimum off time activates at power-
up. To manually override, press the W button
at any time.
Fig. 49. Setup - Outputs - Options - DI Options.
1.3.3.3. DI OPTIONS (digital input options)
The DI Option you select applies to all outputs. This
option overrides any Setpoint/Setback values entered in
the Schedule.
1. Press the X button to display the DI Option selec-
tions.
2. Use the S and T buttons to highlight DISABLE,
SETBACK, or IGNORE.
Default: DISABLE
3. Press the X button to accept the value and display
the SHOW RT option.
When the digital input (DI) closes, all outputs follow the DI
option value (Disable, Setback, or Ignore):
• DISABLE disables the outputs; relays return to de-
energized state and Mod outputs return to 0% output.
• SETPOINT forces the control to the setpoint
temperature.
• SETBACK enables a setback temperature value to be
programmed for each output.
— To program the Setback temperature with Reset,
see Fig. 73 on page 31.
— To program the Setback temperature without
Reset, see Fig. 60 on page 26.
• ENABLE energizes all relays to 100%. Use this option
carefully.
• IGNORE causes the digital input to have no effect on
the Relay or Mod outputs.
M24610A
SETUP
OUTPUTS
OPTIONS
ENTER
MINIMUM
OFF TIME
FOR RELAYS
SETUP
OUTPUTS
OPTIONS
MIN OFF
0
SEC
OR
MIN ON
SETUP
OUTPUTS
OPTIONS
MIN ON
0
SEC
MIN OFF
ENTER
MINIMUM
ON TIME
FOR RELAYS
SETUP
OUTPUTS
OPTIONS
DI OPTS
SETUP
OUTPUTS
OPTIONS
DI OPTS
SELECT DI
OPTIONS
FOR
OUTPUTS
DISABLE
SETPOINT
SETBACK
ENABLE
IGNORE
M24611A