13 - 20
13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
13.4.3 Connecting to CC-Link module
(Q Series) with Ver.1/Ver.2
compatibles mixed
This section describes the setting of the GOT and CC-Link
module (Q Series) with Ver.1/Ver.2 compatibles mixed in
the following system configuration.
CC-Link module (Q Series)
For details of the CC-Link module (Q Series), refer to
the following manual.
CC-Link System Master/Local Module User's
Manual QJ61BT11N
System configuration
*1 The CC-Link module is mounted on the base unit slot 0.
The Start I/O No. of the CC-Link module is set to "0"
When connecting to Q170MCPU
When connected to Q170MCPU, the start I/O No. of
the CC-Link module is set to "70".
Switch setting of CC-Link module (Q Series)
Set the station number setting switch, transmission
speed / mode setting switch.
(1) Station number setting switch
: Necessary : As necessary : Not necessary
(2) Transmission rate/mode setting switch
: Necessary : As necessary : Not necessary
*1 Specify the same transmission speed as that of the GOT.
When the switch setting has been changed
Turn the PLC CPU OFF then ON again, or reset the
PLC CPU.
<CC-Link module>
*1
Type : Master station
Station No. : Station No. 0
Mode : Remote net (Ver.2 mode)
All connect count : 2
Transmission speed : 156kbps
<GOT (Ver.1 compatible)>
(Use default value for settings other than the following.)
Station type : Intelligent device
station
Station No. : Station No. 1
Number of stations
occupied
Exclusive station 1:
:Transmission speed 156kbps
(Use default value for settings other than the following.)
<GOT (Ver.2 compatible)>
(Use default value for settings other
than the following.)
Station type : Intelligent device
station
Station No. : Station No. 2
Number of stations
occupied
Exclusive station 1:
Expanded cyclic setting Single:
:Transmission speed 156kbps
■ [Controller Setting] of GT Designer3
■ Setting of the CC-Link communication unit
■ Switch setting of CC-Link module (Q Series)
■ [Network parameter] of GX Developer
Station number
setting switch
Description Set value
Setting necessity
at GOT connection
Station number
setting
(master station)
0 (fixed)
Transmission
rate/mode setting
switch
Description Set value
Setting necessity
at GOT connection
Transmission
rate/
mode setting
(Online:
156kbps)
*1
0
(1)
(2)
QJ61BT11N
0
5
0
5
0
8
1
2
7
6
5
4
3
STATION
NO.
X10
X1
MODE
QJ61BT11N
RUN
ERR.
SD
MST
L RUN
L ERR.
RD
S MST
NC
DA
DB
NC
SLD
DG
(FG)
C
4