PAGE 14 — GAC3.6HZ 60 HZ GENERATOR• OPERATION AND PARTS MANUAL — REV. #1 (03/31/10)
INSTALLATION
CONNECTING THE GROUND
The nut and ground terminal on the generators should
always be used to connect the generators to a suitable
ground. The ground cable should be #8 size wire
minimum.
At the generator, connect the terminal of the ground cable
between the lock washer and the nut (Figure 2) and tighten
the nut fully. Connect the other end of the ground cable to
a suitable earth ground (ground rod).
120V
240V
120
V
OFF
3600
ACCIRCUITBREAKER
INTERRUPTEURDE
COURANTPRINCIPAL
GAC-3.6H
POWEREDby
HondaEngines
211052
GRPRISEDE
TERRE
ACVOLTMETER
VOLTOMETRECA
ON
OFF
ON
OFF
MARCHE
MARCHE
INTERRUPTEUR
DEOPERATION
OPERATION
SWITCH
CONTROL
DERALENTI
IDLE
CONTROL
ARRET
ARRET
NEUTRALBONDEDTOFRAME
NEUTREMISALAMASSEA
LACARCASSEDUMOTEUR
GROUND ROD
FOR EARTH
GROUND
GENERATOR
GROUND LUG
CONNECT TO
BUILDING
GROUND
IF REQUIRED
8 FT. MINIMUM
REFERENCE
NEC 250-52(C)
GROUND
CABLE
#8 MINIMUM
Figure 2. Generator Grounding