Page 20 of 40
InC1InC1
InC1InC1
InC1 Input Correction: Select
-500-500
-500-500
-500 to
500500
500500
500 °F, °C, or counts. This
feature allows the input value to be changed to agree with
an external reference or to compensate for sensor error.
Note: InC1 is reset to zero when the input type is changed,
or when decimal position is changed.
FiL1FiL1
FiL1FiL1
FiL1 Digital Filter: Select
OFFOFF
OFFOFF
OFF,
11
11
1 to
9999
9999
99. In some cases the time
constant of the sensor, or noise could cause the display to
jump enough to be unreadable. A setting of 2 is usually
sufficient to provide enough filtering for most cases, (2
represents approximately a 1 second time constant). When
the 0.1 degree resolution is selected this should be in-
creased to 4. If this value is set too high, controllability will
suffer.
LPb1LPb1
LPb1LPb1
LPb1 Loop Break Protection: Select
OFFOFF
OFFOFF
OFF,
11
11
1 to
99999999
99999999
9999 seconds. If,
during operation, the output is minimum (0%) or maximum
(100%), and the input moves less than 5°F (3°C) or 5 counts
over the time set for LPb1, the
LOOP bAdLOOP bAd
LOOP bAdLOOP bAd
LOOP bAd message will
appear. The loop break error can be reset by pressing the
ENTER key when at the LPb1 menu item. The INDEX &
ENTER keys may also be used.
If
EditEdit
EditEdit
Edit is set to
11
11
1, jump to
LorELorE
LorELorE
LorE on page 24.
If
EditEdit
EditEdit
Edit is set to
33
33
3, continue.