Display Modes Chapter 3
Opening Previously Stored Transients
The screen below can be accessed with the retrieve button . It displays a list
transients previously stored in the memory.
The status bar at the top displays the memory filled by stored transients.
Name and transient number (from 01…50) for each stored transient.
Transient recording time and date are displayed for each transient.
To select a transient, press the Up/Down Cursor buttons, then press
Enter.
To delete a selected transient, press the Trash Can button , then press
Enter.
Storing the Trigger
The threshold T in percent, defined as an envelope width (over and under) the
last cycle of signal V or A input signal. Its width W is calculated with the nominal
measurement range R for a channel (depending on the selected current sensor).
W = T x R
EXAMPLE
Using the SR193 probe and a 2% trigger level, the width would
be 1000A x 2% = 20 A. Therefore, a deviation of ±20 A will
cause a transient event to be captured.
07/25/02 10:56 100
%
SELECTION OF TRANSIENT
TEST 05
TEST 04
TEST 03
TEST 02
TEST 01
05/07/02 14:31:41
05/07/02 14:31:41
05/07/02 14:31:21
05/07/02 14:31:04
05/07/02 14:31:04
1
2
3