TRG-TRC010-EN 31
period four
Maintenance Considerations
notes
Guideline 3, “
Reducing Emission of Halogenated Refrigerants in Refrigeration
and Air Conditioning Equipment and Systems
,” is one of several advisory
documents published by the American Society of Heating, Refrigerating and
Air-Conditioning Engineers (ASHRAE). This guideline includes a list of
recommended data points to be logged daily for each chiller. Much of this data
may be available from the display on the chiller control panel.
Special attention should be given to:
■ Reviewing the operating log and trends
■ Observing the oil pressure drop to determine if the oil filter needs to be
replaced
■ Monitoring evaporator and condenser approach temperatures
■ Observing and recording the oil level
■ Monitoring purge pump-out operation
operating log
ASHRAE Guideline 3
▲ Chilled water inlet and outlet
temperatures and pressures
▲ Chilled water flow
▲ Evaporator refrigerant
temperature and pressures
▲ Evaporator approach
temperature
▲ Condenser water inlet and
outlet temperatures and
pressures
▲ Condenser water flow
▲ Condenser refrigerant
temperature and pressures
▲ Condenser approach
temperature
▲ Oil pressures, temperature, and
levels
▲ Addition of refrigerant
▲ Addition of oil
▲ Vibration levels
Figure 45