103
RC GROUP - 149_ItEn.0102
Limit thermostat enable temostato limite uscita aria abilitato
outlet air limit thermostat enabled
N N - Y —
Threshold limit thermostat soglia allarme temostato limite uscita aria
outlet air threshold limit thermostat
14°C0÷20°C —
Outlet water limit thermostat termostato limite uscita acqua
outlet water limit thermostat
3°C ±10 °C —
SOGLIE CONTATORI
THRESHOLD HOUR METER
Threshold hour meter soglie contatori
threshold hour meter
Main fan ventilatore principale
main fan
0h 0÷32.000 —
Compr. 1 compressore 1
compressor 1
0h 0÷32.000 —
Compr. 2 compressore 2
compressor 2
0h 0÷32.000 —
Heater riscaldatore elettrico
heater
0h 0÷32.000 —
Humidifer umidificazione
humidification
0h 0÷32.000 —
General alarm 1 allarme genrale 1
general alarm 1
AL1÷AL6
AL1
÷
AL6
YYYYYY N - Y —
AL7÷AL12
AL7
÷
AL12
YYYYYY N - Y —
AL13÷AL18
AL13
÷
AL18
YYYYYY N - Y —
AL19÷AL24
AL19
÷
AL24
YYYYYY N - Y —
AL25÷AL30
AL25
÷
AL30
YY–NYY N - Y —
AL31÷AL36
AL31
÷
AL36
YYYYYY N - Y —
General alarm 2 allarme genrale 2
general alarm 2
AL1÷AL6
AL1
÷
AL6
YYYYYY N - Y —
AL7÷AL12
AL7
÷
AL12
YYYYYY N - Y —
AL13÷AL18
AL13
÷
AL18
YYYYYY N - Y —
AL19÷AL24
AL19
÷
AL24
YYYYYY N - Y —
AL25÷AL30
AL25
÷
AL30
YY–NYY N - Y —
AL31÷AL36
AL31
÷
AL36
YYYYYY N - Y —
Delay ON relay Gen. alarm 1 ritardo attivazione general alarm 1
delay activation general alarm 1
0s 0÷3600 s —
Delay ON relay Gen. alarm 2 ritardo attivazione general alarm 2
delay activation general alarm 2
0s 0÷3600 s —
Buzzer enabling abilitazione cicalino
buzzer enabling
Y N - Y —
Identific. address for supervisor system network
codice di indirizzamento per linea seriale
identification address for serial line
1 000÷200 —
Baud rate velocità trasmissione seriale
baud rate
9600 1200÷19200 —
MP2000 AIR CONDITIONERS
Software per condizionatori d'aria a pompa di calore e Roof Top • EPROM CPX....
• Software for heat pump air conditioners and Roof Top