13. Press the “Up” arrow button until a value of “26” is shown on the screen.
14. Press the “Circle” button. Press the up/down arrow buttons to change the value to the
correct valve that is on the unit. The value number is listed on the valve. The values and
valves are as follows:
0: No valve selected. Alarm A1 will become active.
1: ICM20 with ICAD 600
2: ICM25 with ICAD 600
3: ICM32 with ICAD 600
4: ICM40 with ICAD 900
5: ICM50 with ICAD 900
6: ICM65 with ICAD 900
15. Press the “Circle” button.
The valve is now ready to be used.
Note:
Refer to the appropriate controller manual for control setup.