![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/d/6f/d6faa6be-1d6c-46f6-ab29-188c1dcb57c6/d6faa6be-1d6c-46f6-ab29-188c1dcb57c6-bg15.png)
FS-8700-931 Siemens TIWAY I Page 18 of 23
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Example
// Server Side Connections
Connections
Port, Protocol, Baud, Parity, Handshaking,
P1, TIWAY_BDLC, 9600, None, None,
5.2. Server Side Node Descriptors
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node
Up to 32 alphanumeric
characters
Node_ID
Secondary PLC station address
of physical server node
1-254
Protocol Specify protocol used TIWAY, TIWAY_BDLC
Server_Hold_Timeout*
Specifies time FieldServer will
reserve server side connection
while waiting for the Client side
to update data in Data_Array (if
necessary)
>1.0s
Example
// Server Side Nodes
Nodes
Node_Name, Node_ID, Protocol
PLC_01, 01, TIWAY_BDLC
* Note that no connection information such as the Port is necessary on Server side.