FS-8700-31 Siemens TIWAY I Page 5 of 23
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Example
// Client Side Connections
Connections
Port, Protocol, Baud, Parity, Handshaking, Poll_Delay
P1, TIWAY_BDLC, 9600, None, None, 0.100s
4.3. Client Side Node Descriptors
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node
Up to 32 alphanumeric
characters
Node_ID
Secondary PLC station address to
communicate with
1-254
Protocol Specify protocol used TIWAY, TIWAY_BDLC
Connection
Specify which port the device is
connected to the FieldServer
P1-P8
Example
// Client Side Nodes
Nodes
Node_Name, Node_ID, Protocol, Port
PLC_01, 01, TIWAY_BDLC, P1
4.4. Client Side Map Descriptors
4.4.1. FieldServer Related Map Descriptor Parameters
Section Title
Map Descriptors
Column Title Function Legal Values
Map_Descriptor_Name
Name of this Map
Descriptor
Up to 32 alphanumeric
characters
Data_Array_Name
Name of Data Array
where data is to be stored
in the FieldServer
One of the Data Array names
from “Data Array” section
above
Data_Array_Offset
Starting location in Data
Array
0 to maximum specified in
“Data Array” section above
Function
Function of Client Map
Descriptor
RDBC, WRBC, WRBX, AWT