Regency E21 Gas Fireplace Insert
The Regency E21 may be installed and vented
into any solid fuel fi replace that has been installed
in accordance with the National, Provincial and
local building codes and is constructed of non-
1) Installer must mechanically attach the sup-
plied label to the inside of the fi rebox of the
fi replace into which the gas fi replace insert
2) Do not cut any sheet-metal parts of the
fi replace, in which the gas fi replace insert
3) If the factory-built fi replace has no gas access
hole(s) provided, an access hole of 1-1/2"
(37.5mm) or less may be drilled though the
lower sides or bottom of the fi rebox in a proper
workmanship like manner. This access hole
must be plugged with a non-combustible
insulation after the gas supply line has been
4) The fi replace fl ue damper can be fully blocked
open or removed for installation of the gas
5) The fi replace and fi replace chimney must
be clean and in good working order and
constructed of non-combustible materials.
6) The chimney cleanouts must fi t properly.
7) Refractory (fi rebricks), glass doors, screen
rails, screen mesh and log grates can be
removed from the fi replace before installing
the gas fi replace insert.
8) Smoke shelves, shields and baffl es may be
removed if attached by mechanical fasteners.
If any part is removed it must not weaken
the structural integrity of the factory built.
9) Trim panels or surrounds shall not seal
ventilation openings in the fi replace.
Diagram shows the minimum fi replace opening
required to be able to install the Regency gas
Locate appliance, check Clearances to
Make gas and electrical connections, page
8. Test the pilot. Must be as per diagram,
Install Flue Connector, page 9.
Test Gas pressure, page 10, and check
Test for fl ue spillage, page 11.
Install brick panels (optional), page 11.
Install log set, page 11.
Install Faceplate and Trim, page 12.
Install Flush Door Front (Standard), page
Install Optional Bay Front and optional Bay
Install Louvers (Flush or Bay), pages 13 and
Install optional Wall Switch, Remote Control,
or Wall Thermostat, page 19.
Before leaving this unit with the customer,
the installer must ensure that the appliance is
fi ring correctly and operation fully explained to
Clocking the appliance to ensure the correct
fi ring rate (rate noted on label) after burning
appliance for 15 minutes.
If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow
the unit to burn for 15-20 min. to stabilize.
Ensure that the appliance is venting
CAUTION: Any alteration to the product that
causes sooting or carboning that results
in damage is not the responsibility of the
Note: If you are installing the Molded Faceplate,
the minimum fireplace dimensions are as
: This fi replace has been converted
for use with a gas fi replace insert only and
cannot be used for burning wood or solid fuels
unless all original parts have been replaced,
and the fi replace re-approved by the authority