GE HE500TIU102 Cell Phone User Manual


 
CH. 3: TIU100/101/102/103 06 Apr 2000 PAGE 21
GFK-1819
3.5.1 TIU10X Configuration of the RS-485 Port
The configuration bank (shown in Figure 3.8) sets the parameters of the RS-485 port as described in
Table 3.1.
Table 3.1 Configuration Bank
Switch 1 ON: Pull-up (must be used together with switch 3)
OFF: no Pull-up
Switch 2
ON: 120
termination
OFF: no termination
Switch 3 ON: Pull-down (must be used together with switch 1)
OFF: no Pull-down
Switch 4 Reserved for future use
NOTE:
Switch 1 and 3 must be used together. Either both pull-up and pull-down are
used or neither is used.
Pull-up
and
Pull-down
switches are used to increase the signal level on the RS-485 bus. This is useful if
there is a long bus and a significant amount of attenuation is anticipated.
Figure 3.4 Automation
Equipment Port Receive &
Transmit LEDs
The LEDs flash when the TIU10X
is communicating with the AE.
Figure 3.5 PC Port Receive &
Transmit LEDs
The LEDs flash when the PC is
communicating with the TIU10X
Serial Port
Tx
Rx
PC Port
Tx
Rx
Figure 3.3 Automation Equipment Serial Port