66 PowerMonitor 1000 Unit
Rockwell Automation Publication 1408-IN001E-EN-P - September 2013
Related Functions
•
Log status input changes
• Configuration lock
Configuration Lock Input
Unauthorized changes to the power monitor setup are prevented when the configuration-lock
input terminals, CF and CF1, are connected together.
This feature applies to all models.
Operation
The following set-up parameters and commands are locked when the configuration lock is
applied:
• Analog input setup menu: all parameters
• Advanced setup menu
• Metering result averaging
• Log status input changes
• KYZ setup
• Status input 1 and 2 input scale
• Demand setup
• Ethernet communication set-up menu
• Network demand setup
The following commands are prohibited when the configuration lock is applied:
• Set kWh, kVARh, kVAh register
• Clear all energy registers
• Set status 1 or 2 count
• Clear energy log
• Force KYZ output on, off, or clear force
• Restore factory defaults
• Reset power monitor system
Setup
No setup is needed.