The foundation was designed for:
Outside environment severe exposure
Ambient temperature -10 degrees F to 105 degrees F
Unit weight 20,000 lbs
• RPM 3600
Soil bearing capacity 1,500 lbs/sq.ft.
Wind speed 120 MPH
Exposure factor D
Wind importance factor 1.15
Concrete poured on and permanently cast against the earth
General Design Requirements
The compressor foundation is designed to:
Maintain the compressor in alignment and at proper elevation.
Minimize vibration and prevents its transmission to other structures
Provide a permanently rigid support
• Provide suf cient depth to dampen vibrations.
Foundation