Physical Specifications
Description U.S. International
Height 3.5 inches (2 RU) 89 mm
Width 17.4 inches including bezel
16.7 inches no including bezel
442 mm including bezel
424 mm not including bezel
Depth 20 inches max depth
19 inches to the connector plane
508 mm max depth
483mm to connector plane
Weight, approximate (without PCI cards or
rack mounts)
35lbs (2 disk version)
37.2lbs (4 disk version)
16 kgs (2 disk version)
17 kgs (4 disk version)
Environment Specifications
These are the environmental specifications for the Netra
TM
X4200 server.
Specification Operating Non-Operating
Temperature
5°C to 40°C, (41°F to 104°F)
Short Term -5°C to 55°C (23°F to 131°F)
-40°C to 70°C (-40°F to 158°F)
Relative Humidity
5% to 85% relative humidity, noncondensing
Short term: 5% to 90% relative humidity,
noncondensing, but not to exceed 0.024 kg
water/kg dry air (0.053 lbs. water/2.205 lb. dry
air)
Up to 93% relative humidity
noncondensing, 38°C (100.4°F) max
wet bulb
Altitude
Up to 3000 meters (9,850 feet) @40°C Up to 12,000 meters (40,000 feet)
Power Source Requirements
The Netra X4200 M2 server has two autoranging AC or DC power supplies. To ensure redundant
operation of the power supplies, the two power inputs should be connected to separate power sources.
These are the electrical limits and ranges for the Netra X4200 M2 server utilizing 550W power supplies.
Description AC Specification DC Specification
Operating input voltage range 100 to 240 VAC, 50 to 60 Hz
-48VDC or -60VDC (nominal)
-40VDC to -75VDC (range)
Maximum operating input current 6.5A at 100 to 120 VAC
3.2 A at 200 to 240 VAC
12.7A at -48VDC
10.2A at -60VDC
Maximum heat dissipation 2150 BTU/hr. 2085 BTU/hr.
Just the Facts, August 2007 Sun Confidential: Internal and Sun Channel Partners Use Only 32