Emerson 24VDC Cell Phone User Manual


 
2DOC.IG.QC01.1 Rev.: B December ‘06
En
OK
OK
Fig. 1: Check proper mounting before connecting
air supply and electrical wiring.
OK
OK
Control Module Type Label =
QC01..WP.. = 24VDC
QC01..P4.. = 24VDC Non incendive /
Non Sparking
QC03..P1.. = Intrinsically safe
QC04..P1.. = Intrinsically safe with NAMUR
position feedback
Actuator Type Label =
QS xxxx = Single acting (Spring Return)
QD xxxx = Double acting
1 Applicable Control Modules
Fig. 2 Identification
QC01 - 24 VDC
QC01 - 24 VDC Non-Incendive or
Non Sparking
QC03 - IS Intrinsically safe
QC04 - IS-NAMUR Intrinsically safe with NAMUR
position feedback
2 Before starting
* Be sure that the actuator is correctly mounted
on the valve before connecting air supply and
electrical wiring (see Installation & Operation
Manual FieldQ Valve Actuator, DOC.IOM.Q.E)
* Check the Module label for the right execution
(see figure 2)
* Check the type of actuator: single or double
acting (see figure 2)