A SERVICE OF

logo

35RLC-PRC006-EN
Table P-12. ARI part-load performance for
50 Hz high efficiency
machines in English units
Full Load Full Load
Unit Size Tons EER IPLV
140 140.4 10.2 14.2
155 152.7 10.1 14.2
170 165.2 10.0 14.0
185 183.6 10.1 14.5
200 202.3 10.2 13.9
250 245.5 10.2 15.9
275 274.8 10.3 15.6
300 310.8 10.5 14.7
350 337.9 10.1 15.2
375 375.9 10.3 15.6
400 413.9 10.4 15.5
Table P-11. ARI part-load performance for
50 Hz standard efficiency
machines in English units
Full Load Full Load
Unit Size Tons EER IPLV
140 133.7 9.3 13.4
155 146.2 9.3 13.5
170 159.0 9.2 13.3
185 176.3 9.4 13.8
200 194.0 9.5 13.2
250 234.8 9.6 15.4
275 262.1 9.5 14.7
300 298.6 9.7 14.1
350 324.0 9.4 14.6
375 358.4 9.5 15.0
400 395.5 9.6 14.9
Notes:
1. IPLV values are rated in accordance with ARI Standard
550/590-98.
2. EER and IPLV values include compressors, condenser
fans and control kW.
Performance
Data
Table P-9. ARI part-load performance for
60 Hz standard efficiency
machines in English units
Full Load Full Load
Unit Size Tons EER IPLV
140 138.2 9.7 12.9
155 152.1 9.8 13.3
170 166.2 9.9 13.0
185 181.5 9.7 12.8
200 197.2 9.6 12.7
225 216.9 9.6 13.0
250 237.3 9.6 12.6
275 268.0 9.7 13.3
300 300.2 9.6 13.2
350 340.0 9.6 13.2
400 401.3 9.6 13.7
450 438.3 9.6 13.9
500 479.3 9.6 13.8
Notes:
1. IPLV values are rated in accordance with ARI Standard
550/590-98.
2. EER and IPLV values include compressors, condenser
fans and control kW.
Part Load
Performance
Table P-10. ARI part-load performance for
60 Hz high efficiency
machines in English units
Full Load Full Load
Unit Size Tons EER IPLV
140 143.9 10.3 13.3
155 157.5 10.4 13.6
170 171.3 10.5 13.4
185 187.5 10.3 13.2
200 204.2 10.1 13.0
225 224.4 10.2 13.3
250 243.3 10.1 12.8
275 279.0 10.4 13.8
300 310.2 10.1 13.6
350 346.1 10.4 14.5
400 413.1 10.0 13.9