A SERVICE OF

logo

SSP-PRC001-EN 33
Table ED-5: Unit Wiring with Electric Heat (Single Point Connection) - 5,7 1/2 and 10 Ton Air Handlers
Heater
Model No.
Maximum Fuse
Heater
KW Rating
1
To Use
With Unit
Unit
Power Supply
Control
Stages
Minimum
Circuit Ampacity
2
or HACR Circuit
Breaker Size
2, 6
BAYHTRL106A 4.33/5.76 1 33/37 35/40
BAYHTRL112A 8.65/11.52 TWE060A1 208-230/1/60 1
59/67
3
60/70
BAYHTRL117A 12.98/17.28 TWE060B1 1 88/97 90/100
BAYHTRL123A 17.30/23.04 2
111/127
3
125/150
BAYHTRL106A 4.33/5.76 1 34/38 35/40
BAYHTRL112A 8.65/11.52 1
60/68
3
60/70
BAYHTRL117A 12.98/17.28 TWE090A1 208-230/1/60 1 86/98 90/100
BAYHTRL123A 17.30/23.04 TWE090B1 2
112/128
3
125/150
BAYHTRL129A 21.65/28.80 2
138/158
3
150/175
BAYHTRL106A 4.33/5.76 1 31/41 40/45
BAYHTRL112A 8.65/11.52 1
63/73
3
70/80
BAYHTRL117A 12.98/17.28 TWE120A1 208-230/1/60 1 89/101 90/110
BAYHTRL123A 17.30/23.08 TWE120B1 2
115/131
3
125/150
BAYHTRL129A 21.65/28.80 2
141/161
3
150/175
BAYHTRL305A 3.75/5.00 1 17/19 20/20
BAYHTRL310A 7.45/9.96 TWE060A3 208-230/3/60 1 30/34 30/35
BAYHTRL315A 11.25/14.96 TWE060B3 1 43/49 45/50
BAYHTRL325A 18.71/24.92 2
69/79
3
70/80
BAYHTRL305A 3.75/5.00 1 20/22 20/25
BAYHTRL310A 7.45/9.96 1 33/37 35/40
BAYHTRL315A 11.25/14.96 twE090A3 208-230/3/60 1 46/52 50/60
BAYHTRL325A 18.71/24.92 TWE090B 2
72/82
3
80/90
BAYHTRL335A 26.20/34.88 2
97/112
4
100/125
BAYHTRL305A 3.75/5.00 1 21/23 25/25
BAYHTRL310A 7.45/9.96 1 34/38 35/40
BAYHTRL315A 11.25/14.96 TWE120A3 208-230/3/60 1 47/53 50/60
BAYHTRL325A 18.71/24.92 TWE120B3 2
73/83
3
80/90
BAYHTRL335A 26.20/34.88 2
98/113
4
100/125
BAYHTRL405A 5 1 10 15
BAYHTRL410A 9.96 TWE060A4 460/3/60 1 17 20
BAYHTRL415A 14.96 TWE060B4 1 25 25
BAYHTRL425A 24.92 2 40 40
BAYHTRL405A 5 1 11 15
BAYHTRL410A 9.96 1 19 20
BAYHTRL415A 14.96 TWE090A35 460/3/60 1 26 30
BAYHTRL425A 24.92 TWE090B35 2 41 45
BAYHTRL435A 34.88 2 56 60
BAYHTRL405A 5 1 12 15
BAYHTRL410A 9.96 1 20 20
BAYHTRL415A 14.96 TWE120A35 460/3/60 1 27 30
BAYHTRL425A 24.92 TWE120B35 2 42 45
BAYHTRL435A 34.88 2 57 60
BAYHTRLW05A 5 1 8 15
BAYHTRLW10A 9.96 1 15 15
BAYHTRLW15A 14.96 TWE060AW 575/3/60 1 21 25
BAYHTRLW25A 24.92 2 33 35
BAYHTRLW05A 5 1 11 15
BAYHTRLW10A 9.96 1 17 20
BAYHTRLW15A 14.96 TWE090AW 575/3/60 1 23 25
BAYHTRLW25A 24.92 2 36 40
BAYHTRLW35A 34.88 2 48 50
BAYHTRLW05A 5 1 10 15
BAYHTRLW10A 9.96 1 16 20
BAYHTRLW15A 14.96 TWE120AW 575/3/60 1 22 25
BAYHTRLW25A 24.92 TWE120BW 2 35 35
BAYHTRLW35A 34.88 2 47 50
Electrical
Data
NOTES:
1 kW ratings are at: 208/240V for 208-230V air handlers.
480V for 460V air handlers
600V for 575V air handlers
For other than rated voltage, capacity = ( )
2
x Rated Capacity.
Voltage
Rated Voltage
2 Any power supply and circuits must be wired and protected in accor-
dance with local codes.
3 Field wire must be rated at least 75 C.
4 Field wire must be rated at least 90 C.
5 With motor field converted to 460V.
6 The HACR circuit breaker is for U.S.A. installations only.