6 SSP-PRC001-EN
Application of this product should be
within the catalogued airflow and per-
formance considerations.
Clearance Requirements
The recommended clearances identi-
fied with unit dimensions should be
maintained to assure adequate ser-
viceability, maximum capacity and
peak operating efficiency. Actual
clearances which appear inadequate
should be reviewed with the local
Trane Representative.
180° Blower Rotation
The 5, 7½, and 10 ton air handler blow-
er section can be rotated 180° to
change the discharge pattern. This
modification must be done in the field
and requires an addition of kit. See
unit installer's guide.
Low Ambient
Cooling
As manufac-
tured, these units
can operate to
50° F in the cool-
ing mode of op-
eration. An
accessory head
pressure control
will allow opera-
tion to 0° F out-
door ambient. When
using these units with
control systems such
as bypass changeover
Variable Air Volume,
make sure you consider the
requirement for a head pres-
sure control to allow low ambient
cooling.
Application
Considerations
Typical Horizontal Air Handler Application
Typical Vertical Air Handler Application
Typical Split System Application