54 SSP-PRC001-EN
Table W-3 — Unit and Corner Weights (lbs.)
Note:
1 If application requires steam or hot water heating coils, field suplied isolators must be utilized.
Table W-4 — Accessory Weights (net lbs.)
Note:
1 For use when no supplemental heat is supplied.
2 For use with electric heat.
Tons Unit
Model No.
Shipping
Maximum
(lbs)
Net
Maximum
(lbs)
Corner Weights — Vertical
Corner Weights — Horizontal
1234AB C D
5 TWE060A, B 298 232 59 59 59 59 54 64 64 54
7½ TWE090A, B 388 317 79 79 79 79 73 81 84 77
10 TWE120A, B 439 392 98 98 98 98 95 101 101 95
15 TWE180B 754 692 173 173 173 173 156 174 190 170
20 TWE240B 886 816 204 204 204 204 179 221 228 185
To ns U nit
Model No.
Discharge
Plenum
And
Grille
1
Discharge
Plenum
And
Grille
2
Return
Air Grille
Electric
Heat
Min/Max
Subbase Oversized
Motor
RIS
Isolator
Floor
Mount
RIS
Isolator
Suspended
Mount
Steel Spring
Isolator
Floor Mount
Steel Spring
Isolator
Suspended
Mount
Control
Transformer
5 TWE060A,B 58 93 3 32/43 14 31 2 9
12 6
—
7½ TWE090A,B 73 123 5 27/45 19 48 2 6
12 6 4
10 TWE120A,B 92 156 7 27/45 23 50 2 7
12 6 4
15 TWE180B 124 230 10 79/100 27 80 2 7
12 6
—
20 TWE240B 145 264 12 79/100 31 88 2 9
12 6
—
Weights
Air Handlers
Vertical - 5,7 1/2 & 10 Ton
TWE060A,060B,090A,090B,120A,120B
Vertical - 15 & 20 Ton
TWE0180B,240B
Horizontal - 5,7 1/2 & 10 Ton
TWE060A,060B,090A,090B,120A,120B
Horizontal - 15 & 20 Ton
TWE0180B,240B