Log status input changes
Configuration lock
Configuration Lock Input
Unauthorized changes to the power monitor setup are prevented when the configuration-lock
input terminals, CF and CF1, are connected together.
This feature applies to all models.
Operation
The following set-up parameters and commands are locked when the configuration lock is
applied:
Analog input setup menu: all parameters
Advanced setup menu
Metering result averaging
Log status input changes
KYZ setup
Status input 1 and 2 input scale
Demand setup
Ethernet communication set-up menu
Network demand setup
The following commands are prohibited when the configuration lock is applied:
Set kWh, kVARh, kVAh register
Clear all energy registers
Set status 1 or 2 count
Clear energy log
Force KYZ output on, off, or clear force
Restore factory defaults
Reset power monitor system
Setup
No setup is needed.