PowerMonitor 1000 Unit 67
Rockwell Automation Publication 1408-IN001E-EN-P - September 2013
Miscellaneous Functions
The power monitor includes a small number of miscellaneous functions that you can select.
Set-up parameters of these functions are in the Advanced Configuration set-up menu.
Parameter Description Range Default User
Setting
New Password Select a new password if desired to help prevent
unauthorized changes to the unit setup.
0…9999 0
Metering Result
Averaging
If enabled, metering results are averaged by using the
previous eight cycles to smooth the results.
0 = Off
1 = On
1
Log Status Input
Changes
(1)
(1) Log status input changes parameter is not accessible from the LCD screen.
If disabled, prevents routine status input changes from
filling up the status log. Useful when a status input is used
for pulse counting or demand EOI synch.
0 = Disable
1 = Enable
0
Unit Error Action Determines the unit’s response to a hardware or firmware
error.
0 = Halt, make status indicator solid red
1 = Reset the unit
0…1 1
Software Error Log
Full Action
Determines the unit response when a firmware failure is
detected and the error log is full.
0 = Halt on error and wait for clear log command, make
status indicator solid red
1 = Perform a firmware reset
0…1 1