November 28, 2011
7038-159D
Page 35
5700 Step Top Wood Stove Series ACC
• Must be a 6 inch (152mm) diameter (ID) high
temperature chimney listed to UL 103 HT (2100
o
F)
or ULC S629M.
• Must use components required by the manufacturer
for installation.
• Must maintain clearances required by the manufacturer
for installation.
• Refer to manufacturers instructions for installation.
D. Factory-Built Chimney
The chimney can be new or existing, and must meet the
following minimum requirements.
Figure 35.1 - Factory-Built Exterior Chimney
Floor
Protector
Chimney
Connector
Insulated " T "
Flashing
Listed Termination Cap
Trim Collar on
Inside Wall
Listed Chimney
Storm Collar
Wall Support
Roof Brace (if required)
Floor
Protector
Chimney
Connector
Ceiling Support
Listed Chimney
Listed Termination Cap
Storm Collar
Flashing
NOTICE: In Canada when using a factory-built chim-
ney it must be safety listed, Type UL103 HT (2100
o
F)
[1149
o
C] CLASS “A” or conforming to CAN/ULC-S629,
STANDARD FOR 650
o
C FACTORY-BUILT CHIM-
NEYS.
Figure 35.2 - Factory-Built Interior Chimney
WARNING! Risk of Fire!
Inspection of Chimney:
• Chimney must be in good condition and meets the
minimum standard of NFPA 211.
• Factory-built chimney must be 6 inches (152mm)
UL103 HT.
WARNING! Risk of Asphyxiation!
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE
SERVING ANOTHER APPLIANCE.
DO NOT CONNECT TO ANY AIR DISTRIBUTION
DUCT OR SYSTEM.
This may allow fl ue gases to enter the house.