![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/0/9c/09cc9d98-76d0-41e9-8945-1d03c47fa5e2/09cc9d98-76d0-41e9-8945-1d03c47fa5e2-bg83.png)
6.1.4 Interface Specifications (GT01)
Interface for connecting PLC/External devices
- COM port
Item
AIGT0030B1/AIGT0030H1
AIGT0030B/AIGT0030H
AIGT0130B1/AIGT0130H1
AIGT0130B/AIGT0130H
AIGT0230B1/AIGT0230H1
AIGT0230B/AIG0230H
AIGT0032H1
AIGT0132B1
AIGT0132H1
AIGT0232B1
AIGT0032H
AIGT0132B
AIGT0132H
AIGT0232B
Communication standard
Conforms to RS232C
(Non insulation type)
Conforms to RS422
(Non insulation type)
Communication
condition with
external devices
9600, 19200, 38400, 57600, 115200 bps
Transmission distance
(Total length)
Max. 15 m
(Baud rate: 19,200 bit/s)
(Baud rate:
(Baud rate:
Protocol
- MEWTOCOL (Protocol for PANASONIC PLC: FP series)
- General-purpose serial (PANASONIC dedicated protocol)
- Other companies’ PLC protocols (For the details, refer to the
Connector terminal base (8-pin)
Note1) 2) 3)
Note1) The (+) and (-) terminals are the power supply terminals for driving the main unit.
Note2) Regarding power supply voltage, please pay due consideration to the cable length so that the
applied voltage is within the operation voltage range.
Note3) Wen supplying power from a power supply separate from the PLC, make sure the power cable is
no longer than 10 m. (5 V DC type only)
Interface for transferring screen data
- TOOL port
Conforms to RS232C (Non insulation type)
Conditions for
communications
with GTWIN
9600, 19200, 115200, 230400 bps
Note1) 2)
Note1) The baud rate of 230400 bps is available when the USB/RS232C conversion cable is used.
Note2) When the baud rate is set to 230400 bps, the connection using the GTWIN automatic
communication setting function is not possible. Set the GTWIN communication setting to 230400
bps, and then transfer data.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net