Honeywell 805595 Cell Phone User Manual


 
IQ8Wireless transponder for wall mounting
FB 798941 / 10.06 31
LED 1
Operation (green)
Lits in normal operation
LED 2
Common fire alarm (red)
Lits when the fire alarm of an assigned wireless device has been detected.
The relay >common fire alarm< is activated.
LED 3
Common trouble (yellow), display not latched
Lits when a fault message from the IQ8Wireless transponder or an assigned
wireless device has been detected. Activation of the >common fault< relay is
interrupted and the relay contact changes position.
LED 4
Initialisation (yellow)
Lits during the switch-on/learning process of the IQ8Wireless transponder while the
wireless devices are being recognised.
c
Housing screw to open/close the transponder housing
LED-indicators on the board
A
Status indication of the Analog loop communication
Both LED (red and green) twinkle while the data communication on the connected
loop of the FACP IQ8Control is active.
red green
LED-incicator for the wireless operation mode
B
Off
flashes
(2Hz)
Normal operation mode
All assigned wireless devices operates as required in
the frequenzy-hopping mode.
ON
flashes
(2Hz)
Normal operation with a communication fault
At least one wireless device is out of the frequenzy-
hopping mode and is automatically searched in the
base channel. This fault is indicated at the FACP
after approx. 40-60s. If the wireless device could be
automatically found within this time the red LED goes
out.
Flashes alternately
(2Hz)
Installation mode (restricted operation)
e.g. during field strength measurement, transponder
or detector data assignment or while searching a
wireless device.
Flashes common
(2Hz)
Malfunction – Wireless mode disabled
Wireless communication not possible Î transponder
is defect (return to factory)
Flashes common
each 7 seconds
Disablement – wireless mode off
The wireless operation mode is automatically
disabled due to no wireless is assigned or present.