Honeywell 805595 Cell Phone User Manual


 
IQ8Wireless transponder for wall mounting
40 FB 798941 / 10.06
11.1 Analog loop
1. Connect the IQ8Wireless transponder to the analog loop of the IQ8Control fire alarm
system and the external power supply as described in "Installation".
2. Switch on the fire alarm control panel or the analog loop to which the IQ8Wireless
transponder is connected. If several IQ8Wireless transponders are connected, start these
up one after the other to prevent multiple assignment of one wireless device.
3. Conduct a wiring recognition of the loop with the service PC and the tools 8000
programming software. All devices on the analog loop are displayed.
4. Click the required IQ8Wireless transponder on this analog loop to open the dialog for
programming the wireless transponder.
5. In the menu item “Measure signal strength” check if the quality of the wireless
transmission between the transponder and the base is adequate.
6. All the wireless bases that this IQ8Wireless transponder has recognised are displayed in
menu item "Assign wireless devices“. If several IQ8Wireless transponders exist, wireless
bases that are already assigned to other IQ8Wireless transponders are not shown.
7. In the menu item “Assign wireless devices”, assign all required wireless bases to the
IQ8Wireless transponder individually. The wireless devices can be assigned individually in
individual detector zones.
8. Start-up is complete for this wireless transponder. Leave the IQ8Wireless transponder
switched on and start up any other IQ8Wireless transponders that you have.
805595
I
Q
8
C
o
n
tr
o
l
I
Q
8
C
o
n
tr
o
l
esserbus
®
-PLus
Service PC
Panel
Interface
789862
Fig. 25: Commissioning
Î
Analog loop connection