E. Align the Microswitch with the holes in the
Auxiliary Switch Mounting Bracket, as shown.
Secure the Microswitch to the Auxiliary Switch
Mounting Bracket using the (2) .138-32 × 1.00"
screws, (4) flat washers, (2) lock washers, and
(2) nuts supplied.
F. Connect the two (2) wires (with ring terminals)
from the External Harness to the Auxiliary
Switch. Connect one wire to the normally
“Closed” terminal and the other wire to the
“Common” terminal.
G. Align the Auxiliary Switch Assembly with the
holes drilled in the top and middle Breaker
Shelves in Step 5-B. Secure the Auxiliary
Switch Assembly to the Breaker using the (2)
.190-16 × .500" thread cutting screws, (2) lock
washers, and (2) flat washers supplied. When
Installing the Auxiliary Switch Assembly, insure
that the Microswitch Arm is above the Breaker
Cross Bar.
For All Breakers.
H. Use the wire ties supplied to secure all
harnesses and wires away from moving parts
within the Breaker.
Fig. 54 Microswitch Mounted to the Auxiliary
Switch Mounting Bracket
Fig. 55 External Harness Wires Connected to the
Auxiliary Switch
Fig. 56 Auxiliary Switch Installed on the Breaker