Confirm that the PowerNet communication
wiring is correct by following the
procedures detailed in Section 7.4 of the
Instructions for the Application of Digitrip RMS
Retrofit Kits on Power Circuit
Breakers. Note that for 810 and 910 Kits, the
impedance between COM 1 and COM 2
should be between one (1) and three (3) ohms.
When testing is complete, disconnect the
External Harness from the Cell Harness. Final
External Harness connection will be performed
later in the Retrofit Process.
For Kits Supplied with a Cell Harness Only.
STEP 15: MOUNTING THE CELL HARNESS
A. The Cell Harness is to be mounted in the
Breaker Cell. The connector end is to be
mounted on the right front side of the Cell, in a
location suitable for connection with the Exter-
nal Harness. The Terminal Blocks can be
mounted anywhere space is available in the
Cell as long as connection to the External
Harness can be made.
B. Route the Cell Harness wiring to keep it away
from any moving parts within the Cell Housing.