NOTE: Approximately 5% of the system airflow draws from the rear of the system and exits
the top of the system.
Figure 2-2 Airflow Diagram
A thermal report for the HP Integrity Superdome/sx2000 server is provided in Table 2-17
(page 57).
Table 2-17 Physical Environmental Specifications
Condition
Overall System
Dimensions
(W X D X H)
WeightMaximum
Airflow at
32
o
C
1,2
Nominal Airflow
2
Voltage
200–240 V ac
Typical Heat
Release
mminkgpoundsm
3
/hrCFMm
3
/hrCFMWattsDescription
76.2x121.9x195.630x48x77.2420.3926.35.029005.029003423Minimum
Configuration
76.2x121.9x195.630x48x77.2563.21241.25.029005.029009130Maximum
Configuration
76.2x121.9x195.630x48x77.2515.11135.25.029005.029006968Typical
Configuration
2 Cell, 4 DIMM, 2 I/OMinimum
Configuration
3
ASHRAE Class
1
8 Cell, 32 DIMM, 4 I/OMaximum
Configuration
3
6 Cell, 16 DIMM, 4 I/OTypical
Configuration
3
Environmental Requirements 57