Note: The following calculation is performed in the relay for phase angle correction.
Setting Calculation Remarks
0 Ia = Ia
1
Ia = (Ia – Ic)/
3
2
Ia = Ic
3
Ia = (Ic + Ib)/
3
4 Ia = Ib
5
Ia = (Ib – Ia)/
3
6
Ia = Ia
7
Ia = (Ia + Ic)/
3
8 Ia = Ic
9
Ia = (Ic – Ib)/
3
10
Ia = Ib
11
Ia = (Ia – Ib)/
3
0
1
2
3
4
5
6
7
8
9
10
11
Ia