Emerson MP2-115HW Carrying Case User Manual


 
15
SPECIFICATIONS
This POD is intended for use with a UPS meeting all of the following
requirements:
UPS input cord is compatible with the rating and type of receptacle
on the POD labeled “CONNECT UPS LINE CORD HERE.”
UPS output receptacle is compatible with the POD input power con-
nector labeled “UPS.”
Available utility is compatible with the POD input connection and
an appropriately sized branch circuit breaker has been provided.
Product Warranty Registration
To register for warranty protection:
•Visit the Quick Links section of our Web site at:
http://www.liebert.com
Click on Product Warranty Registration and fill in the form.
If you have any questions, please contact us at:
US: 800-222-5877
Outside the US: 614-841-6755
upstech@liebert.com
Transfer Time (to and from
maintenance bypass)
< 6 milliseconds
Operating Ambient Temperature
32°F to 104°F (0°C to +40°C)
Storage Ambient Temperature
-4°F to 140°F (-20°C to +60°C)
Dimensions with brackets
W x D x H: in. (mm)
3.5 x 3.0 x 15.5 (88.0 x 77.0 x 394.0)
Humidity
0 to 95% non-condensing
Agency/Standards
UL1778, c-UL, ISTA Procedure 1A
Electrical Rating
See Model Label on POD
Table 1 Breaker specifications
Model
VA -
Volt
Rating
Input
Current
Rating
at
120V*
Recommended
(Maximum)
External
Overcurrent
Protection
Recommended
Wire (including
ground wire)
(75°C
copper wire)
Maximum
Wire
Accepted
by Terminal
Block
Terminal
Tightening
Torque
MP2-115HW 12A 15A 14 AWG 8 AWG 20 in-lb
MP2-120HW 16A 20A 12 AWG 8 AWG 20 in-lb
MP2-130HW 24A 30A 10 AWG 8 AWG 20 in-lb
* See POD Rating Plate for Alternate Output Voltages