15
SPECIFICATIONS
This POD is intended for use with a UPS meeting all of the following
requirements:
• UPS input cord is compatible with the rating and type of receptacle
on the POD labeled “CONNECT UPS LINE CORD HERE.”
• UPS output receptacle is compatible with the POD input power con-
nector labeled “UPS.”
• Available utility is compatible with the POD input connection and
an appropriately sized branch circuit breaker has been provided.
Product Warranty Registration
To register for warranty protection:
•Visit the Quick Links section of our Web site at:
http://www.liebert.com
• Click on Product Warranty Registration and fill in the form.
If you have any questions, please contact us at:
US: 800-222-5877
Outside the US: 614-841-6755
upstech@liebert.com
Transfer Time (to and from
maintenance bypass)
< 6 milliseconds
Operating Ambient Temperature
32°F to 104°F (0°C to +40°C)
Storage Ambient Temperature
-4°F to 140°F (-20°C to +60°C)
Dimensions with brackets
W x D x H: in. (mm)
3.5 x 3.0 x 15.5 (88.0 x 77.0 x 394.0)
Humidity
0 to 95% non-condensing
Agency/Standards
UL1778, c-UL, ISTA Procedure 1A
Electrical Rating
See Model Label on POD
Table 1 Breaker specifications
Model
VA -
Volt
Rating
Input
Current
Rating
at
120V*
Recommended
(Maximum)
External
Overcurrent
Protection
Recommended
Wire (including
ground wire)
(75°C
copper wire)
Maximum
Wire
Accepted
by Terminal
Block
Terminal
Tightening
Torque
MP2-115HW 12A 15A 14 AWG 8 AWG 20 in-lb
MP2-120HW 16A 20A 12 AWG 8 AWG 20 in-lb
MP2-130HW 24A 30A 10 AWG 8 AWG 20 in-lb
* See POD Rating Plate for Alternate Output Voltages