DATAVIEW Software Chapter 4
Transients Configuration
The Transients window allows you to set up the criteria for capturing transients.
Figure 8 - Transients Window
1. Type a name for the session, up to seven characters.
2. Select the date and time to end the search for transients.
3. Select the percent deviation for voltage and current transients.
The choices available from the drop down window are 1, 2, 5, 10, 20, 50,
and 100% of the full scale range of measurement.
Refer to
Tr ans ie nt Mo de on page 37 for detailed information on these
values.
4. Select the maximum number of transients to capture (from 1…50).
– Clear Screen: Clears the fields that were already entered for a new
transient search. This button doesn't cause any changes on the
PowerPad unit.
– Write Changes and Start New Transient Search: Initiates searching
from new transients when the OK or Apply button is pressed.
– View Transients: View the PowerPad unit's stored transients.
Download and delete transients options are also available.
EN50160 Configuration
The EN50160 standard defines limiting values and permissible variations of the
voltage quality for the European Community. It defines which parameters are
relevant, and how are they measured. Continuous or random sampling control of
the voltage quality provides the supplier of electric energy with a reliable basis
when dealing with network problems, and it contributes to quality assurance.