4 – OPERATOR SERVICE
39
Error Message
Displayed
Error Explanation &
Possible Causes
What To Check &
Corrective Action To Clear
Error
043 OPEN CIRCUIT
PLATFORM CCW
The Lower Control has detected an open circuit on the
Platform CCW solenoid output when it was energized
during startup self diagnostics.
NOTE: A load of less than 70mA will be detected as
an open circuit. The typical load is approximately
800mA.
Possible causes include:
1. Faulty Platform CCW solenoid wiring
2. Faulty Platform CCW solenoid
3. Faulty Lower Control
1. Repair or replace Platform CCW solenoid
wiring
2. Replace Platform CCW solenoid
3. Replace Lower Control
044 SHORTED CIRCUIT
PLATFORM CCW
The Lower Control has detected excessive current on
the Platform CW solenoid output when it was
energized during startup self diagnostics.
Possible causes include:
1. Faulty Platform CCW solenoid wiring
2. Faulty Platform CCW solenoid
3. Faulty Lower Control
1. Repair or replace Platform CCW solenoid
wiring
2. Replace Platform CCW solenoid
3. Replace Lower Control
045 OPEN CIRCUIT
TURNTABLE CW
The Lower Control has detected an open circuit on the
Turntable CW solenoid output when it was energized
during startup self diagnostics.
NOTE: A load of less than 70mA will be detected as
an open circuit. The typical load is approximately
800mA.
Possible causes include:
1. Faulty Turntable CW solenoid wiring
2. Faulty Turntable CW solenoid
3. Faulty Lower Control
1. Repair or replace Turntable CW solenoid wiring
2. Replace Turntable CW solenoid
3. Replace Lower Control
046 SHORTED CIRCUIT
TURNTABLE CW
The Lower Control has detected excessive current on
the Turntable CW solenoid output when it was
energized during startup self diagnostics.
Possible causes include:
1. Faulty Turntable CW solenoid wiring
2. Faulty Turntable CW solenoid
3. Faulty Lower Control
1. Repair or replace Turntable CW solenoid wiring
2. Replace Turntable CW solenoid
3. Replace Lower Control
047 OPEN CIRCUIT
TURNTABLE CCW
The Lower Control has detected an open circuit on the
Turntable CCW solenoid output when it was energized
during startup self diagnostics.
NOTE: A load of less than 70mA will be detected as
an open circuit. The typical load is approximately
800mA.
Possible causes include:
1. Faulty Turntable CCW solenoid wiring
2. Faulty Turntable CCW solenoid
3. Faulty Lower Control
1. Repair or replace Turntable CCW solenoid
wiring
2. Replace Turntable CCW solenoid
3. Replace Lower Control
048 SHORTED CIRCUIT
TURNTABLE CCW
The Lower Control has detected excessive current on
the Turntable CCW solenoid output when it was
energized during startup self diagnostics.
Possible causes include:
1. Faulty Turntable CCW solenoid wiring
2. Faulty Turntable CCW solenoid
3. Faulty Lower Control
1. Repair or replace Turntable CCW solenoid
wiring
2. Replace Turntable CCW solenoid
3. Replace Lower Control