![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/7/e4/7e4f09e5-2cbc-46d8-934f-9c9031bdf248/7e4f09e5-2cbc-46d8-934f-9c9031bdf248-bg10.png)
3-2 Comm Parameter Calculator Errors (LCL)
LCL# Description
1
Can not compute communication port control byte.
[LCL#1]
Failure to compute the CP (Communication Property) port
configuration. Make sure your standard transceiver database
(stdxcvr.xml) has not been corrupted. An update might be
available at the www.lonmark.org website. Contact LonSupport
if problem persists.
2 Unrecognized encoded clock rate value <id> [LCL#2]
Bad encoded value for clock speed (5 for 10MHz, 6 for 20MHz,
etc).
3
The transceiver's general purpose data record seems
malformed: <gp data> [LCL#3]
The xcvr_gp_data in STDXCVR.XML seems malformed. Make
sure your standard transceiver database (stdxcvr.xml) has not
been corrupted. An update might be available at the
www.lonmark.org website. Contact LonSupport if the problem
persists.
4
The device's clock rate (encoded value <id>) and the
transceiver's communication rate (encoded value <id>)
result in an invalid communication clock divider value.
One of the two input rates must be invalid. [LCL#4]
The comm_rate from STDXCVR.XML and effective hardware
clock rate combination results in an invalid comm clock divider
value. One of the two must be wrong. Verify the hardware
preferences. Make sure your standard transceiver database
(stdxcvr.xml) has not been corrupted. An update might be
available at the www.lonmark.org website. Contact LonSupport
if problem persists.
5
Unable to determine <attribute> using transceiver <xcvr
name> [LCL#5]
The aspect described as <attribute> cannot be computed as
part of the communication parameter calculations. Make sure
your standard transceiver database (stdxcvr.xml) has not been
corrupted. An update might be available at the
www.lonmark.org website. Contact LonSupport if problem
persists.
6
The transceiver requires a minimum clockrate which is
higher than the device's configured input clock speed.
[LCL#6]
The hardware clock speed is lower than the required minimum
for this transceiver. Choose a higher clock rate, or choose a
different transceiver type.