5. BASE SPECIFICATIONS PARAMETERS
II - 30
# Items Details Setting range (unit)
1065 JOG_H JOG
response
type
Set up an improved JOG response type.
0: Conventional specification
The system is started and stopped by signal via
ladder without reference to external input
signals.
1: Type 1
The system is started up and stopped by
external signal.
2: Type 2
The system is started up and stopped by
performing the AND operation for external
signals and those via ladder.
3: Type 3
The system is started up when signals via
ladder rise. It is stopped when external signals
and those via ladder fall.
4: Type 4
Zero point return mode: The system is started
up and stopped by signal via ladder without
reference to external input signals
(conventional specification).
Non-zero point return mode: The system is
started up and stopped by performing AND
for external signals and those via ladder
(type 2).
0 to 4
1066 JOG_HP Select JOG
activation
(+) device
Specify the number of the device that inputs +JOG
activation signals. The device type is specified by
JOG_D in #1071. The effective range of set values
vary depending on the device type. A value outside
of the effective range is invalid if specified.
X: 0000 to 013F
(hexadecimal)
M: 0000 to 5119
(decimal)
1067 JOG_HN Select JOG
activation
(−) device
Specify the number of the device that inputs -JOG
activation signals. The device type is specified by
JOG_D in #1071. The effective range of set values
vary depending on the device type. A value outside
of the effective range is invalid if specified.
X: 0000 to 013F
(hexadecimal)
M: 0000 to 5119
(decimal)
1068
(PR)
slavno Not used.