Operation and Troubleshooting Chapter 4
Table 24 - SMC-50 Controller Fault Codes
Display Fault HIM or
Software
Fault Code
Enabled Possible Causes Possible Solutions
Line Fault with
Phase Indication
1, 2, 3 Prestart
and
Running
Missing supply phase
Motor not connected properly
Incoming 3-phase voltage
instability
Check for open line (i.e. blown fuse)
Check for open load lead
Verify power quality
Shorted SCR
with Phase
Indication
4, 5, 6 All Shorted power module Check for shorted SCR, replace power module if necessary
Open Gate with
Phase Indication
7, 8, 9 Start or
Stop
Open gate circuitry
Loose gate lead
Perform resistance check; replace power module if
necessary
Check gate lead connections to the control module
PTC Power Pole
and SCR
Overtemp
10 or 60 Controller ventilation blocked
Controller duty cycle exceeded
Fan failure
Ambient temperature limit
exceeded
Failed thermistor
Check for proper ventilation
Check application duty cycle
Wait for motor to cool or provide external cooling
Replace power module or control module as needed
Replace fan
Motor PTC 59 Running Motor ventilation blocked
Motor duty cycle exceeded
PTC open or shorted
Check for proper ventilation
Check application duty cycle
Wait for motor to cool or provide external cooling then check
resistance of PTC
No Load Fault 14, 15, 16, 17 Prestart
Only
Loss of load side power wiring
with phase indication (15=A, 17=C)
Start command cycled
unexpectedly with motor rotating
Check all load side power connections
Check motor windings
Voltage
Unbalance and/
or Current
Imbalance
18 and/or 42 Running Supply unbalance is greater than
the user-programmed value
The delay time is too short for the
application
Check power system and correct if necessary, then correct
the
user-programmed value
Extend the delay time to match the application requirements
Overvoltage 19 Running Supply voltage is greater than the
user-programmed value
The delay time is too short for the
application
Check power system and correct if necessary, otherwise
correct the user-programmed value
Extend the delay time to match the application requirements
Undervoltage 20 Running Supply voltage is less than the
user-programmed value
The delay time is too short for the
application
Check power system and correct if necessary, otherwise
correct the user-programmed value
Extend the delay time to match the application requirements
Overload 21 Running Motor overloaded
Overload parameters are not
matched to the motor
Check motor overload condition
Check values for overload class and motor FLC and verify
current draw of the motor
Underload 22 Running Broken motor shaft, belts, tool
bits, etc.
Pump cavitation
Incorrect user setting
Check pump system, machine drive components, and loading
Check settings
Repair or replace motor
Jam 23 Running Motor current has exceeded the
user-programmed jam level
Correct source of jam or excessive loading and check
programmed time value
Stall 24 Running Motor did not reach full speed by
the end of the programmed ramp
time
Incorrect user setting
Check pump system, machine drive components, and
loading. Repair or replace motor, if necessary.
Check settings
Phase Reversal 25 Prestart
only
Incoming supply voltage is not the
expected ABC sequence
Check power wiring and correct if necessary