Rockwell Automation Publication 150-QS003D-EN-P - November 2013 53
Appendix
A
SCCR Ratings
SCCR Ratings
Table 26 - SCCR (High Capacity Fault) Electrical Ratings
Type 1 Coordination
SCPD Performance Class J or Class L Fuse Inverse Time (Thermal Magnetic) Circuit Breaker
SCCR List
(High Capacity Fault)
Maximum
Available
Fault (600V) [kA]
Amps 480V, 65kA Maximum
Typical Max. Bul. 140U
Frame Size
Max.
Amps
Cat. No. Rating Plug
Line Device
Operational
Current Rating
[A]
90 100 150 200 M 350 140U-M6D3-D35 not required
110 175 225 300 140U-M6D3-D30 not required
140 225 300 400 140U-M6D3-D40 not required
180 300 400 400 140U-M6D3-D40 not required
210 350 450 M 600 140U-M6D3-D60 not required
260 450 500 700 140U-M6D3-D70 not required
320 500 700 800 140U-M6D3-D80 not required
361 601 800 N 1000 140U-N6L3-E12 140U-NRP3-E10
420 700 800 1200 140U-N6L3-E12 140U-NRP3-E12
520 800 1000 1200 140U-N6L3-E12 140U-NRP3-E12
Delta Device
Operational
Current Rating
[A]
155 65 250 300 M 450 140U-M6D3-D45 not required
190 300 400 500 140U-M6D3-D50 not required
242 400 500 700 140U-M6D3-D70 not required
311 500 600 700 140U-M6D3-D70 not required
363 601 800 N 1000 140U-N6L3-E12 140U-NRP3-E10
450 700 1000 1200 140U-N6L3-E12 140U-NRP3-E12
554 800 1200 1200 140U-N6L3-E12 140U-NRP3-E12
625 1000 1200 R 1600 140U-R6L3-E20 140U-R20RP3-E16
727 1200 1600 2000 140U-R6L3-E20 140U-R20RP3-E20
900 1200 2000 2000 140U-R6L3-E20 140U-R20RP3-E20
Basic Requirements for Type 1 Coordination: Under the short-circuit condition, the starter shall cause no danger to persons or the installation. The
starter may not be suitable for further service without repair or replacement of parts. For further details, See UL508/CSA C22.2 No. 14 and EN 60947-4-2.
Consult local codes for proper sizing of short-circuit protection.
High capacity fault ratings when used with a time delay Class J fuse or time delay Class L fuse.
Circuit Breaker must be of the designated 140U Frame
Other circuit breakers pending.