Allen Company SMC-50 Cell Phone User Manual


 
56 Rockwell Automation Publication 150-QS003D-EN-P - November 2013
Chapter A Repair/Replacement Parts
Other Components
To protect the Smart Motor Controller (SMC) and/or motor from line voltage surges, protective modules may be
placed on the line, load, or both sides of the SMC. Do not place protective modules on the load side of
the SMC when using an inside-the-delta motor connection or with pump, linear deceleration, or braking
control.
Component Description
Catalog
Number
Option Modules
PTC, ground fault, current feedback 150-SM2
Analog I/O module, 2 inputs/2 outputs 150-SM3
Digital I/O, four 120/240V AC inputs, three relay outputs 150-SM4
Parameter Configuration — DIP & rotary dial 150-SM6
Replacement Control
Wiring Terminal Blocks
(module as shipped
includes terminal block)
Control Wiring
Terminal Block for:
Control module 150-SCMRTB
PTC, ground fault, current
feedback module
150-SM2RTB
Analog I/O module 150-SM3RTB
Digital I/O module 150-SM4RTB
Line/Load Surge
Protective Module
480V AC, 90 A and greater 150-F84L
600V AC, 90 A and greater 150-F86L
IEC Terminal Cover
IEC line and/or load terminal cover for 90...180 A devices,
dead front protection, (IP2X (finger safe) with 250MCM
wire)
150-STCB
Control Module Cover Replacement control module front cover 150-SCMRC
Controller Cover Replacement controller cover for 210…320 A units 150-SCRC
Replacement controller cover for 361…520 A units 150-SDRC
Fan Cover Replacement fan cover for 90…180 A units 150-SBFC
Replacement fan cover for 210…320 A units 150-SCFC
Replacement fan cover for 361…520 A units 150-SDFC