Exhaust system
Whenever possible, install the ironer along an outside wall where duct length can be kept to a minimum, and
make-up air can be easily accessed. The construction must not block the airow at the rear of the ironer.
Doing so would prevent adequate air supply to the ironer combustion.
For maximum efciency, ironer air must be exhausted to the outdoors by the shortest possible route.
Note
Never connect an ironer duct at a 90° angle to the collector dust (see picture below).
Doing so will cause excessive back pressure, resulting in poor performance.
Never connect two ironer exhaust ducts directly across from each other at the point of
entry to the collector dust.
Number of ironers D1 D2 D3
Diameter of the exhaust pipe (in mm) 100 150 225
Ventilation aperture required section (in dm²) 0,8 1,8 4